HP EVA3000 User Manual Page 79

  • Download
  • Add to my manuals
  • Print
  • Page
    / 165
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 78
1
0130a
2
3
5
4
5
Figure 25 Dual PDU assembly
1. PD U 1
2. PDU 2
3. Circuit breakers 4. AC receptacles
5. Mounting hardware
PDU 1
PDU 1 connects to AC power distribution source 1. A PDU 1 failure:
Disables the power distribution circuit.
Removes po
werfromPDMs1,2,and3.
Disables PS 1 in the drive enclosures.
Disables the upper controller power supply.
PDU 2
PDU 2 connects to AC power distribution source 2. A PDU 2 failure:
Disables the power distribution circuit.
Removes power from PDMs 4, 5, and 6.
Disables PS 2 in the drive enclosures.
Disables the lower controller power supply.
PDMs
There are six PDMs mounted in the rear of each rack:
Three m
ounted on the left vertical rail connect to PDU 1.
Three m ounted on the right vertical rail connected to PDU 2.
Each PDM has eight AC receptacles and one thermal circuit breaker. The PDMs distribute the AC power
from the PDUs to the enclosures. Two power sources exist for each controller pair and drive enclosure. If
aPDUfa
ils, the system will remain operational.
CAUTION:
TheACpowerdistributionwithinarackensuresabalancedloadtoeachPDUandreducesthepossibility
of an overload condition. Changing the cabling to or from a PDM cou ld cause an overload condition.
HP supports only the AC power distributions dened in this user guide.
HP StorageWorks 3000/5000 Enterprise Virtual Array user guide (VCS 4.xxx)
79
Page view 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 164 165

Comments to this Manuals

No comments