Periodic maintenance 62
Periodic maintenance
Periodic maintenance overview
Perform periodic inspections on the components in this section to ensure that the HP POD 40c NA continues
to perform within the designed parameters.
Qualified personnel
Qualified personnel are identified as personnel who are:
Properly trained in the operation and maintenance of the HP POD 40c NA
Customer-authorized to conduct maintenance activities
Qualified personnel can be:
HP personnel
Agents for HP
Site maintenance personnel
Cooling system maintenance schedule
Component to be inspected Task Frequency Capable Party
Air filters
Inspect and replace as necessary Quarterly, or as
needed
Qualified personnel
Air filter differential pressure
sensor
Inspect and test, replace as
necessary
Annually Qualified personnel
Cooling system leak check
Verify there is no visible chilled
water leak from:
Heat exchanger
Cold water supply piping
Cold water return piping
If a leak is detected, see "Leak
detection maintenance (on page
63)"
Quarterly Qualified personnel
Condensate drain pans
Inspect pans:
Free of debris
No leaks
Leakage detectors are in
proper position
Clean pans as necessary
Quarterly Qualified personnel
Condensate drain pan sensors
Inspect and test, replace as
necessary
If a leak is detected, see "Leak
detection maintenance (on page
63)"
Quarterly Qualified personnel