HP 40cp User Manual Page 67

  • Download
  • Add to my manuals
  • Print
  • Page
    / 79
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 66
Periodic maintenance 67
Component to be inspected Task Frequency Capable Party
Suppression system
Suppression system test As required by
local code
Authorized technician
Fire-pull visual and operational
inspection
As required by
local code
Authorized technician
Fire strobe and horn visual and
operational inspection
As required by
local code
Authorized technician
HP POD 40c NA structure
Component to be inspected Task Frequency Capable Party
Complete structure
Visually inspect the structural
integrity.
Annually Qualified personnel
Inspect the door operation and
inspect the door gaskets for water
and air leaks.
Annually Qualified personnel
Visually inspect the paint. Perform
prep and touch-up as necessary.
Annually Qualified personnel
Life safety
Component to be inspected Task Frequency Capable Party
Manual EPO shunt trip
EPO FUNCTIONAL TEST (POD will
power down)
Manually initiate EPO with the
internal and external push buttons
(if installed) in succession. (Verify
all shunt-trips on all panels trip.)
Annually Qualified personnel
Thermal EPO shunt trip
EPO
FUNCTIONAL TEST (POD will
power down)
Initiate a thermal (automatic) EPO
shutdown via the EPO
temperature switches located in
the hot aisle. (Verify all shunt-trips
on all panels trip.)
Annually Qualified personnel