HP Performance-Optimized Datacenter
User Guide
Part Number 510055-001
March 2009 (First Edition)
Page view 0
1 2 3 4 5 6 ... 62 63

Summary of Contents

Page 1 - User Guide

HP Performance-Optimized Datacenter User Guide Part Number 510055-001 March 2009 (First Edition)

Page 2 - Intended audience

Safety considerations 10 Safety considerations Safety information The HP POD has been listed to the UL 69050 as an Information Technology Product an

Page 3 - Contents

Safety considerations 11 CAUTION: All customer supplied water fittings must be composed of carbon steel, stainless steel, or copper. Do not use ca

Page 4 - Contents 4

Component identification 12 Component identification HP POD components HP POD components Item Component Description 1 Drain lines Collect wate

Page 5 - Contents 5

Component identification 13 If any of the racks within the HP POD contain empty U space, you must use a heavy duty filler panel to avoid compromisin

Page 6 - Site requirements

Component identification 14 Internal emergency components Item Component Description 1 Internal fire strobe and horn (x2) Indication of a fire a

Page 7 - Site requirements 7

Component identification 15 Item Component Description 4 ASSD panel (on page 36) Air sampling smoke detection system 5 EPO button Cuts off all

Page 8 - Environmental considerations

Component identification 16 Item Component Description 2 Transformer Transforms power from 480V at your facility to the 415V needed for the HP PO

Page 9 - Component documentation

Installation 17 Installation HP POD contents The following items are shipped with the HP POD, and are delivered at the time of your HP POD delivery a

Page 10 - Safety considerations

Installation 18 Component Quantity Part number Side panel 50U kit 1 AN991A 50U rack bracket kit 21 AP014A Either of the following busway dropbox

Page 11 - Safety considerations 11

Installation 19 • Pipe wrench Installing the HP POD using the optional components The following steps are an overview of the installation procedure

Page 12 - Component identification

© Copyright 2009 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Page 13 - HP POD emergency components

Installation 20 3. Pump domestic or industrial water into the water distribution kit closed-loop system fill tank, according to the water quality req

Page 14 - HP POD panel locations

Installation 21 6. Open the bleeder valve on the HP POD return line. 7. When the tank is full and there is no more air coming out of the bleeder va

Page 15

Installation 22 9. Connect the facility supply and return lines to the water distribution kit. 10. Connect the water distribution kit to your facil

Page 16

Installation 23 11. (Optional) Connect the HP POD humidifier to the domestic or industrial water drain (1) and supply (2) lines. For more information

Page 17 - Installation

Installation 24 Each connection is labeled. Two of the conduits power the electrical busway breakers and one powers the house panel. 3. Turn on fac

Page 18 - Preinstallation checklist

Installation 25 5. Close the main breaker in the House panel on the exterior of the HP POD. 6. Close the remaining breakers in the House panel one

Page 19 - Connecting the water

Installation 26 • Test the operation of the analog and digital phone system • Verify initial IT start-up • Conduct an infrared scan of all electri

Page 20

Cooling system 27 Cooling system HP POD cooling system CAUTION: Contaminated supply water might cause decreased cooling capacity or disruption i

Page 21 - Installation 21

Cooling system 28 2. Pull the overhead down. Condensation management CAUTION: During operation, avoid leaving the HP POD doors open, to minimi

Page 22 - Installation 22

Cooling system 29 WARNING: Any water that drains around the HP POD causes a potential slip hazard. Use caution where slip hazards are present. W

Page 23 - Connecting the power

Contents 3 Contents Site requirements ...

Page 24 - 3. Turn on facility power

Water quality requirements 30 Water quality requirements Water quality requirements and specifications • Closed-loop water must not contain any lim

Page 25 - Commissioning the HP POD

Water quality requirements 31 Frost damage To avoid frost damage, the water temperature must not be allowed to fall below the minimum permissible te

Page 26 - Verify initial IT start-up

Power management 32 Power management Electrical busway The electrical busway is a modular, overhead electrical distribution system that supplies pow

Page 27 - Cooling system

Power management 33 • To disable power to a single PDU, turn off the main switch on that PDU. • To disable power to a single rack, open the main b

Page 28 - HP POD drains

Power management 34 The high density HP POD includes an additional electrical busway in the center of the unit. High density HP POD Feature Specif

Page 29 - Leak detection

Power management 35 Panels The following panels are on the exterior of the HP POD. Item Component Description 1 Electrical busway enclosed cir

Page 30 - Water quality requirements

Power management 36 ASSD panel The ASSD panel draws air from the piping network inside the HP POD and monitors the smoke levels in the air. If smoke

Page 31 - Water temperature

Power management 37 To enable remote access to the EPO system, switch to Bypass mode. Callout Component Description 1 Power On LED Indicates th

Page 32 - Power management

Power management 38 Armed mode—Pressing a red EPO button on the POD causes the following events: • The red System Alarm/EPO Shutdown light on the E

Page 33 - Power distribution

Power management 39 Security panel location If you decide you want to install a security panel, the HP POD has a predesignated location for a securi

Page 34 - Rack power

Contents 4 Water precautions...

Page 35 - Item Component Description

Building management system 40 Building management system Using a building management system (BMS) NOTE: If your site does not have a BMS, then

Page 36 - EPO Panel

Building management system 41 For more information, see the junction control system documentation included in the Operations & Maintenance Man

Page 37 - EPO modes

Building management system 42 Alarm Meaning Solution Fan failure One of the fans is not working. If you are still within your service contract,

Page 38 - House panel

Building management system 43 4. After a 30-second delay, the HP POD releases the suppressant gas, if the optional fire suppressant system is instal

Page 39 - Security panel location

Optional components 44 Optional components Additional insulation You can choose to have additional insulated paint added to your HP POD prior to shi

Page 40 - Building management system

Optional components 45 Each external panel is secured through key lock hardware. The following locations have been prewired for your own security up

Page 41 - BMS alarms

Optional components 46 Water distribution kit power requirements Callout Specification 1 30 AT, 30 AF, 3P 2 Within facility 480V, 3 phase power

Page 42 - Safety and security alarms

Frequently asked questions 47 Frequently asked questions HP POD frequently asked questions Question Answer Can I keep the HP POD on the trailer? Y

Page 43

Frequently asked questions 48 Question Answer Is the HP POD weather resistant? If there is an external leak, the HP POD is weatherproof and has suf

Page 44 - Optional components

Troubleshooting 49 Troubleshooting HP POD troubleshooting Issue Resolution The water is not flowing, or flowing too slowly. Verify that all applicab

Page 45 - Water distribution kit

Contents 5 Air and water heat exchanger maintenance... 5

Page 46 - Callout Specification

Specifications 50 Specifications HP POD specifications Features Specifications Dimensions 40 ft x 8 ft x 9.5 ft Maximum weight 30,000 lb (empty)-

Page 47 - Frequently asked questions

Specifications 51 Feature Specification Number of input circuit breakers 2: 1 per panel Protection percentage 80% Amps (per breaker) 400A Fir

Page 48 - • Audible—Horn

Specifications 52 Feature Specification Humidifier 3.79 l/hr (1 gal/hr) domestic water from an alternate supply source Rack specifications Standar

Page 49 - Troubleshooting

Specifications 53 Environmental specifications Features Specifications Operating temperature -18ºC to 54ºC (0ºF to 130ºF) Non-operating temperature

Page 50 - Specifications

Maintenance 54 Maintenance Periodic maintenance Perform periodic inspections of the POD to ensure there is no sign of overheating. During periodic in

Page 51 - Water specifications

Maintenance 55 Before you contact HP Be sure to have the following information available before you call HP: • Technical support registration number

Page 52 - Rack specifications

Regulatory compliance notices 56 Regulatory compliance notices Regulatory compliance identification numbers For the purpose of regulatory compliance

Page 53 - Environmental specifications

Regulatory compliance notices 57 • Low Voltage Directive 2006/95/EC • EMC Directive 2004/108/EC • Machinery Directive 98/37/EEC Compliance with t

Page 54 - Maintenance

Regulatory compliance notices 58 Chinese notice Class A equipment Korean class A notice Japanese class A notice

Page 55 - Before you contact HP

Acronyms and abbreviations 59 Acronyms and abbreviations AHJ Authority Having Jurisdiction ASHRAE American Society of Heating, Refrigerating and Ai

Page 56

Site requirements 6 Site requirements Optimum environment Specific environmental requirements must be met to provide optimum performance with minimu

Page 57 - BSMI notice

Acronyms and abbreviations 60 NEMA National Electrical Manufacturers Association PDU power distribution unit POD Performance-Optimized Datacenter

Page 58 - Japanese class A notice

Index 61 A acceptable water quality specifications 30 air and water heat exchanger maintenance 54 air filter sensor 44, 54 alarms, BMS 41 ala

Page 59 - Acronyms and abbreviations

Index 62 I installation 17 installing the POD at your facility 19 insulation 44 J Japanese notice 58 K kit contents 17 Korean notices 58

Page 60

Index 63

Page 61 - Index 61

Site requirements 7 • Cooling water • Power • Drain (optional) Available to connect to central facility infrastructure • BMS via BacNet protoco

Page 62 - Index 62

Site requirements 8 Callout Connection 2 Chilled water return connection 3 Chilled water supply connection 4 IT cable portals∗ ∗There are identic

Page 63 - Index 63

Site requirements 9 Leveling requirements The site location for the HP POD must be level +/- 0.5 degree tolerance. Grounding requirements IMPORT