HP Performance-Optimized Datacenter User Guide Part Number 510055-001 March 2009 (First Edition)
Safety considerations 10 Safety considerations Safety information The HP POD has been listed to the UL 69050 as an Information Technology Product an
Safety considerations 11 CAUTION: All customer supplied water fittings must be composed of carbon steel, stainless steel, or copper. Do not use ca
Component identification 12 Component identification HP POD components HP POD components Item Component Description 1 Drain lines Collect wate
Component identification 13 If any of the racks within the HP POD contain empty U space, you must use a heavy duty filler panel to avoid compromisin
Component identification 14 Internal emergency components Item Component Description 1 Internal fire strobe and horn (x2) Indication of a fire a
Component identification 15 Item Component Description 4 ASSD panel (on page 36) Air sampling smoke detection system 5 EPO button Cuts off all
Component identification 16 Item Component Description 2 Transformer Transforms power from 480V at your facility to the 415V needed for the HP PO
Installation 17 Installation HP POD contents The following items are shipped with the HP POD, and are delivered at the time of your HP POD delivery a
Installation 18 Component Quantity Part number Side panel 50U kit 1 AN991A 50U rack bracket kit 21 AP014A Either of the following busway dropbox
Installation 19 • Pipe wrench Installing the HP POD using the optional components The following steps are an overview of the installation procedure
© Copyright 2009 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties
Installation 20 3. Pump domestic or industrial water into the water distribution kit closed-loop system fill tank, according to the water quality req
Installation 21 6. Open the bleeder valve on the HP POD return line. 7. When the tank is full and there is no more air coming out of the bleeder va
Installation 22 9. Connect the facility supply and return lines to the water distribution kit. 10. Connect the water distribution kit to your facil
Installation 23 11. (Optional) Connect the HP POD humidifier to the domestic or industrial water drain (1) and supply (2) lines. For more information
Installation 24 Each connection is labeled. Two of the conduits power the electrical busway breakers and one powers the house panel. 3. Turn on fac
Installation 25 5. Close the main breaker in the House panel on the exterior of the HP POD. 6. Close the remaining breakers in the House panel one
Installation 26 • Test the operation of the analog and digital phone system • Verify initial IT start-up • Conduct an infrared scan of all electri
Cooling system 27 Cooling system HP POD cooling system CAUTION: Contaminated supply water might cause decreased cooling capacity or disruption i
Cooling system 28 2. Pull the overhead down. Condensation management CAUTION: During operation, avoid leaving the HP POD doors open, to minimi
Cooling system 29 WARNING: Any water that drains around the HP POD causes a potential slip hazard. Use caution where slip hazards are present. W
Contents 3 Contents Site requirements ...
Water quality requirements 30 Water quality requirements Water quality requirements and specifications • Closed-loop water must not contain any lim
Water quality requirements 31 Frost damage To avoid frost damage, the water temperature must not be allowed to fall below the minimum permissible te
Power management 32 Power management Electrical busway The electrical busway is a modular, overhead electrical distribution system that supplies pow
Power management 33 • To disable power to a single PDU, turn off the main switch on that PDU. • To disable power to a single rack, open the main b
Power management 34 The high density HP POD includes an additional electrical busway in the center of the unit. High density HP POD Feature Specif
Power management 35 Panels The following panels are on the exterior of the HP POD. Item Component Description 1 Electrical busway enclosed cir
Power management 36 ASSD panel The ASSD panel draws air from the piping network inside the HP POD and monitors the smoke levels in the air. If smoke
Power management 37 To enable remote access to the EPO system, switch to Bypass mode. Callout Component Description 1 Power On LED Indicates th
Power management 38 Armed mode—Pressing a red EPO button on the POD causes the following events: • The red System Alarm/EPO Shutdown light on the E
Power management 39 Security panel location If you decide you want to install a security panel, the HP POD has a predesignated location for a securi
Contents 4 Water precautions...
Building management system 40 Building management system Using a building management system (BMS) NOTE: If your site does not have a BMS, then
Building management system 41 For more information, see the junction control system documentation included in the Operations & Maintenance Man
Building management system 42 Alarm Meaning Solution Fan failure One of the fans is not working. If you are still within your service contract,
Building management system 43 4. After a 30-second delay, the HP POD releases the suppressant gas, if the optional fire suppressant system is instal
Optional components 44 Optional components Additional insulation You can choose to have additional insulated paint added to your HP POD prior to shi
Optional components 45 Each external panel is secured through key lock hardware. The following locations have been prewired for your own security up
Optional components 46 Water distribution kit power requirements Callout Specification 1 30 AT, 30 AF, 3P 2 Within facility 480V, 3 phase power
Frequently asked questions 47 Frequently asked questions HP POD frequently asked questions Question Answer Can I keep the HP POD on the trailer? Y
Frequently asked questions 48 Question Answer Is the HP POD weather resistant? If there is an external leak, the HP POD is weatherproof and has suf
Troubleshooting 49 Troubleshooting HP POD troubleshooting Issue Resolution The water is not flowing, or flowing too slowly. Verify that all applicab
Contents 5 Air and water heat exchanger maintenance... 5
Specifications 50 Specifications HP POD specifications Features Specifications Dimensions 40 ft x 8 ft x 9.5 ft Maximum weight 30,000 lb (empty)-
Specifications 51 Feature Specification Number of input circuit breakers 2: 1 per panel Protection percentage 80% Amps (per breaker) 400A Fir
Specifications 52 Feature Specification Humidifier 3.79 l/hr (1 gal/hr) domestic water from an alternate supply source Rack specifications Standar
Specifications 53 Environmental specifications Features Specifications Operating temperature -18ºC to 54ºC (0ºF to 130ºF) Non-operating temperature
Maintenance 54 Maintenance Periodic maintenance Perform periodic inspections of the POD to ensure there is no sign of overheating. During periodic in
Maintenance 55 Before you contact HP Be sure to have the following information available before you call HP: • Technical support registration number
Regulatory compliance notices 56 Regulatory compliance notices Regulatory compliance identification numbers For the purpose of regulatory compliance
Regulatory compliance notices 57 • Low Voltage Directive 2006/95/EC • EMC Directive 2004/108/EC • Machinery Directive 98/37/EEC Compliance with t
Regulatory compliance notices 58 Chinese notice Class A equipment Korean class A notice Japanese class A notice
Acronyms and abbreviations 59 Acronyms and abbreviations AHJ Authority Having Jurisdiction ASHRAE American Society of Heating, Refrigerating and Ai
Site requirements 6 Site requirements Optimum environment Specific environmental requirements must be met to provide optimum performance with minimu
Acronyms and abbreviations 60 NEMA National Electrical Manufacturers Association PDU power distribution unit POD Performance-Optimized Datacenter
Index 61 A acceptable water quality specifications 30 air and water heat exchanger maintenance 54 air filter sensor 44, 54 alarms, BMS 41 ala
Index 62 I installation 17 installing the POD at your facility 19 insulation 44 J Japanese notice 58 K kit contents 17 Korean notices 58
Index 63
Site requirements 7 • Cooling water • Power • Drain (optional) Available to connect to central facility infrastructure • BMS via BacNet protoco
Site requirements 8 Callout Connection 2 Chilled water return connection 3 Chilled water supply connection 4 IT cable portals∗ ∗There are identic
Site requirements 9 Leveling requirements The site location for the HP POD must be level +/- 0.5 degree tolerance. Grounding requirements IMPORT