Installation 20
3.
Pump domestic or industrial water into the water distribution kit closed-loop system fill tank,
according to the water quality requirements (on page 30).
NOTE: The HP POD pipe design is rated for a maximum pressure rating of 150 psi.
4. Verify that your facility water pressure is within the acceptable range (20-25 psi).
5. Initiate the system pumps on the water distribution kit:
o Manually initiate the system pumps with the main power switch located on the pumps.
- or -
o Connect the water distribution kit to the BMS system, and initiate the system pumps through the
BMS.