HP Performance Optimized Datacenter 40c G2 User Guide Abstract This guide is intended for the person who operates and maintains the HP Performance O
Component identification 10 Top view shown Item Component Description 1 Exit sign locations Indicates the location of an exit 2 Fire strobe lig
Component identification 11 Top view shown Electrical power component identification Front view shown Item Component Description 1 Fire box*
Component identification 12 Item Component Description 4 415 Y/240 V 3-phase, 4-wire, 800 A electrical panel Feed B power for critical IT loads (e
Component identification 13 Front view shown Item Electrical safety label Description 1 Input power Lists the input power information 2 Panel s
Component identification 14 Control cabinet component identification Item Component Description 1 VESDA air sampling smoke detection unit An ear
Component identification 15 CAUTION: If any racks contain empty RU space, use the HP POD 40c G2 filler panels to maintain the efficiency of the HP
Life safety systems 16 Life safety systems Life safety overview The HP POD 40c G2 has multiple life safety systems that all work together to protect
Life safety systems 17 The EPO system must be reset before you can power up and restart the HP POD 40c G2. To reset the EPO system: 1. Verify that
Life safety systems 18 Item Component Indicator color Description 7 EPO mode Key control Enables you to select the EPO mode: • Armed • Test •
Life safety systems 19 Manual fire pulls The HP POD 40c G2 includes two fire pulls. One fire pull is located next to the personnel access door and
© Copyright 2012 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties
Life safety systems 20 IMPORTANT: The VESDA filter must be changed regularly to ensure accurate smoke detection readings. For more information abo
Life safety systems 21 Fire suppression sequence of operations After the fire suppression system is activated by a VESDA signal or a manual fire pul
Power, electrical, and controls 22 Power, electrical, and controls Site electrical system To ensure a complete and safe integration of the HP POD so
Power, electrical, and controls 23 A certified electrician must test and verify that the HP POD 40c G2 is properly grounded. Lightning protection
Power, electrical, and controls 24 Capacities HP POD 40c G2 capacity limitations The capacity limitations for the HP POD 40c G2 are separated into t
Power, electrical, and controls 25 Top view shown The top of each electrical panel has four 10.16 cm (4 in) welded couplings where the power feeder
Power, electrical, and controls 26 Front view shown Arc flash safety The customer must complete an arc flash assessment of the HP POD 40c G2 and t
Power, electrical, and controls 27 Feature Specification Frequency 60 Hz Amps (per busway) 200 A Voltage (per busway) 415 V Grounding Copper Busway
Power, electrical, and controls 28 Control cabinet power components Item Component Description 1 VESDA power supply and battery backup Provides
Power, electrical, and controls 29 Top view shown The HP POD 40c G2 electrical busways can be configured for non-redundant power or redundant power
Contents 3 Contents Overview ...
Power, electrical, and controls 30 • Redundant power installation (2N load)—Four busways are powered from one power feed, and the remaining four bu
Power, electrical, and controls 31 • To disable power to all racks, open the breaker for each busway on the corresponding electrical panel on the H
Power, electrical, and controls 32 All emergency lights are tied to the battery backup power, keeping the interior of the HP POD 40c G2 illuminated
Environmental control system 33 Environmental control system Environmental control system overview The ECS developed for the HP water-cooled POD is
Environmental control system 34 By connecting your HP POD 40c G2 to a BMS system, you can monitor the various parameters and alarms. For more inform
Environmental control system 35 Top view shown Item Sensor Quantity Description 1 Differential pressure sensor probes 12 • Monitors the hot an
Environmental control system 36 Heat exchanger temperature sensors There are two contact temperature sensors per heat exchanger. One temperature sen
Environmental control system 37 Managing the ECS from the HP POD 40c G2 The ECS interface is viewed directly from the ECS screen on the control cabi
Environmental control system 38 b. Double-click Local Area Connection. c. Select Internet Protocol (TCP/IP). d. Click Properties. e. Select Use
Environmental control system 39 g. Click OK. 3. Click OK to save changes and close the TCP/IP Properties screen. 4. Click OK to close the Local A
Contents 4 HP POD 40c G2 lighting ...
Environmental control system 40 4. Click Connect. Locating the ECS IP addresses IMPORTANT: The ECS has three NIC addresses: 10.10.10.1, 10.10.
Environmental control system 41 Password protection The ECS has two levels of security: • Customer • Service The following screens are available u
Environmental control system 42 Item Icon name Description 1 Zone (#) power supply status Navigates directly to the Power Details screen for
Environmental control system 43 Overview screen The Overview screen appears upon activation of and displays an overview of the ECS components and th
Environmental control system 44 Information Description Average cooling system performance data Indicates cooling system sensor averages System sta
Environmental control system 45 Status Overview screen The Status Overview screen displays the status of all system component alarms. For more infor
Environmental control system 46 The Basic System Configuration screen enables you to configure the basic alarm parameters and the definition of unit
Environmental control system 47 To configure the cold aisle low temperature alarm parameters: 1. Select Cold Aisle Low Alarm Temperature. A keypad
Environmental control system 48 To configure the low differential pressure parameters: 1. Select Difference Pressure Low Alarm. A keypad appears. 2
Environmental control system 49 To configure the chilled water supply low temperature alarm parameters: 1. Select Chilled Water Supply Low Alarm Te
Contents 5 Periodic maintenance ...
Environmental control system 50 The Advanced System Configuration screen displays the static IP address for each power meter, fan controls, and othe
Environmental control system 51 Calibrating the flowmeter This option enables flow rate calibration based on the value of a calibrated flow meter. T
Environmental control system 52 Enable/disable power management The current power management setting appears on the Enable/disable Power Management
Environmental control system 53 To set the HP POD 40c G2 serial number in the ECS: 1. Select POD S/N. A keypad appears. 2. Enter the HP POD 40c G2
Environmental control system 54 CAUTION: Making changes to the ECS in the service-level area can cause the cooling system components to fail. Only
Environmental control system 55 Alarm Meaning Solution EPO The EPO system activates and the HP POD 40c G2 shut down. 1 Follow the emergency proce
Cooling system 56 Cooling system HP POD 40c G2 cooling system theory of operation CAUTION: Using contaminated supply water can cause decreased c
Cooling system 57 The minimum HP server inlet temperature is 10°C (50°F). For non-HP equipment, consult the documentation for that equipment. Water
Cooling system 58 Feature Specification Facility input temperature to the HP POD 40c G2 12ºC to 24ºC (55ºF to 75ºF) Working pressure 1,034 kPa (1
Cooling system 59 Side view shown Item Component Description 1 Heat exchanger Use chilled facility water to cool the air in the HP POD 40c G2 2
Overview 6 Overview Before you begin For more information on site requirements, specifications, power requirements, management requirements, and sup
Cooling system 60 Depending on the IT equipment you have installed in your HP POD 40c G2, you can choose to change both default parameters to improv
Cooling system 61 The HP POD 40c G2 has two heat exchanger condensate drains. IMPORTANT: You might need to connect the HP POD 40c G2 drain dire
IT networking and communications 62 IT networking and communications Networking Connecting the HP POD 40c G2 to the facility network is a vital part
IT networking and communications 63 Connection portal diameter Connection point Quantity 5.08 cm (2 in) portal Communication connection for all com
IT networking and communications 64 End view shown You must make the connections between the facility and the HP POD 40c G2. For configuration and
Optional components 65 Optional components Fire protection system The fire protection system is a HP POD 40c G2 self-contained system, with no conne
Power up procedure 66 Power up procedure Standard HP POD 40c G2 power up procedure This procedure is for your reference only and assumes that the PO
Power up procedure 67 Site electrical Close all POD site power feeder breakers and monitor for any effects that are not standard. Site chilled wate
Power up procedure 68 This process ensures personnel safety during the electrical start up of the HP POD 40c G2. WARNING: To avoid risk of perso
Power up procedure 69 IMPORTANT: To allow the POD ambient temperature to be raised in a controlled manner, open the chilled water supply and retur
Overview 7 CAUTION: If any racks contain empty RU space, use the HP POD 40c G2 filler panels to maintain the efficiency of the HP POD 40c G2 therm
Power up procedure 70 Power down procedure 1. Power down all IT equipment. 2. Open all POD power drop box breakers. 3. Monitor the system paramet
Specifications 71 Specifications General HP POD 40c G2 specifications Features Specifications Overall dimensions • Height—3.66 m (12 ft) • Lengt
Specifications 72 Fire alarm panel connections The electrical layout of the fire alarm system is as described in the schematic drawing supplied with
Specifications 73 Feature Specification Non-operating temperature* -29ºC to 54ºC (-20ºF to 130ºF) Operating humidity • 0% to 100% external • 10%
Maintenance 74 Maintenance Periodic maintenance Perform periodic inspections to ensure that the HP POD 40c G2 continues to perform according to desi
Contacting HP 75 Contacting HP Before you contact HP Be sure to have the following information available before you call HP: • Active Health System
Regulatory compliance notices 76 Regulatory compliance notices HP POD 40c G2 regulatory compliance The HP POD 40c G2 complies with the following reg
Regulatory compliance notices 77 • The HP POD 40c G2 meets the following ratings: Feature Specification Category Rated Overvoltage Category III P
Regulatory compliance notices 78 Regulatory requirements for EXIT signs Manufacturers of tritium EXIT signs are “specific licensees,” meaning they a
Glossary 79 Glossary AHJ authority having jurisdiction branch circuit The conductors and components following the last overcurrent protective devic
Component identification 8 Component identification Structural component identification The HP POD 40c G2 documentation frequently refers to the spe
Glossary 80 equipment A general term, including fittings, devices, appliances, luminaires, apparatus, machinery, and the like used as a part of, or
Glossary 81 UPS uninterruptible power system
Documentation feedback 82 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat
Index 83 A access 65 alarms, ECS 54 B basic system configuration 45 before you begin 6 before you contact HP 75 buttons 8 C cables, FCC
Index 84 life safety systems 16 lightning protection 23 locating the ECS IP address 40 logging in to ECS 39 M maintenance 74 maintenance s
Component identification 9 • Regulatory compliance identification number—This product has been assigned a unique regulatory model number and is loc