HP Data Center Environmental Edge User Manual Page 74

  • Download
  • Add to my manuals
  • Print
  • Page
    / 113
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 73
Menu bar actions 74
Item Action
Edits alert
Activates alert
Deactivates alert
Deletes alert
Creating an alert definition
Observer has several predefined alerts within the application that cannot be changed or deleted from the
system. The only action items for the predefined alerts is to activate, deactivate, or dismiss the alert. The
following alerts are predefined.
Predefined alert Description
UNKNOWN All errors that are not otherwise defined.
AUDIT Notifies an administrator if any software component is
not running or is configured incorrectly. The default
notification interval is every 5 minutes, though the
interval can be adjusted in HP Insight Environmental
Configurator.
Sensor requires
service
A sensor on the HP Rack Sensor Array requires service.
Warning Front
Temperature
Rack front temperature is outside the recommended
range. The default range is between 18°C and 27°C
(64.4°F and 80.6°F). You can adjust the temperature
range in HP Insight Environmental Configurator.
Critical Front
Temperature
Rack front temperature is outside the recommended
range. The default range is between 18°C and 27°C
(64.4°F and 80.6°F). You can adjust the temperature
range in HP Insight Environmental Configurator.
DAL_ERROR Notifies an administrator of any critical issue with any
software component.
Circuit Current
above threshold
Notifies an administrator if the current of any circuit that
is monitored by BCMS is above the configured
threshold.
Circuit Power above
threshold
Notifies an administrator if the power of any circuit that
is monitored by BCMS is above the configured
threshold.
Circuit Power Factor
below threshold
Notifies an administrator if the power factor of any
circuit that is monitored by BCMS is below the
configured threshold.
Communication
error
Notifies an administrator if one or more data points
cannot be acquired. This alert is generated by wired
plug-ins such as Modbus, SNMP, XML, and web
services that are used in communicating data.
Circular
dependency in CRE
rule
Notifies an administrator when circular dependency is
detected in a CRE rule. This alert is generated if the PUE
calculation graph is configured incorrectly. For more
Page view 73