Metric Affected objects Description
greater the possibility that the equipment experiences
temperatures above the maximum allowable temperature, as
determined by ASHRAE.
Rack Cooling Index
LO
®
Data center racks
Zone racks
RCI
LO
TM/SM
is the complement to RCI
HI
TM/SM
to draw attention to
the supply air that is below the minimum recommended
temperature, as determined by ASHRAE.
RCI
HI
®
/RCI
LO
®
Inlet
Measurement Count
Data center racks
Zone racks
The number of racks that have RCI
HI
TM/SM
or RCI
LO
TM/SM
measurements
Average Rack Inlet
Temperature
Zone racks The average of the top, middle, and bottom rack inlet
temperature sensors on each rack for each zone
Average Rack
Discharge
Temperature
Zone racks The average of the top, middle, and bottom rack discharge
temperature sensors on each rack for each zone
Min, Max, Average
Rack Top Inlet Dew
Point
Data center racks
Zone racks
Dew point calculated at the top inlet on each rack for each
zone
Min, Max, Average
Rack Cold Top Inlet
Air Temp Rate of
Change
Data center racks
Zone racks
Rack top inlet temperature degrees change per hour, for each
zone
Min, Max, Average
CRAC supply
temperature
CRAH/CRAC
Zone
Supply temperatures calculated for each zone
Min, Max, Average
CRAC return
temperature
CRAH/CRAC
Zone
Return temperatures calculated for each zone
Min, Max, Average
CRAC supply dew
point temperature
CRAH/CRAC
Zone
Dew point temperatures for supply air for each zone
Min, Max, Average
CRAC return dew
point temperature
CRAH/CRAC
Zone
Dew point temperatures for return air for each zone
Custom Metrics tab
The Custom Metrics tab only appears at the data center level, if you have defined and configured custom
calculation inspectors in the HP Insight Environmental Configurator. For more information, see the HP
Insight Environmental Configurator User Guide.
The Custom Metrics tab displays:
All data inspectors configured for the data center
Historical data for the monitored calculation groups
Accessing the Custom Metrics tab