The report is automatically generated based on sensor readings. It provides estimated battery life for all
object batteries and suggests recommended replacement parameters.
The scroll bar enables you to see the entire report.
Right-click a row to access the context menu, and then select from the menu.
Replacing batteries
Observer sensor objects require approved lithium batteries for long lifetime, such as Energizer or
Eveready L-91 batteries. When replacing the batteries in a sensor object, use the same battery type.
1. Do not disconnect the sensors or remove the sensor object from its installed location.
2. Press and lift the tabs on both sides to remove the battery cover.
Inside the battery cover is the diagram that illustrates which pairs of batteries to remove to enable the
object to continue reporting data.
CAUTION: If you remove the left or right pair of batteries instead of the inside or outside pair,
the sensor object loses power and cannot report data to the Observer.
3. Remove the inside pair of batteries (1) and replace with new lithium batteries.
4. Remove the outside pair of batteries (2) and replace with new lithium batteries.