HP StorageWorks 2500 Disk System Enclosure User Manual Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 89
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
1. Ready
2. Online
3. Fault
Figure 28 Disk drive status indicators
Table 11 Di
sk drive status indications
Ready Online Fault
Description
On On
Off
Normal operational status.
Drive is idle.
Flashing
On
Off
Normal op
erational status.
Drive is b
eing accessed.
On On On
Displays on the first disk in the enclosure to indicate
the disk drive is not connected to either I/O module.
Verify the FC cable connections to an HBA.
On
Off
Flashing
Indicates disk drive error/not active.
Verify FC loop continuity.
Catastrophic errors
The design of the DS2500 allows it to continue operating in the presence of faulty hardware. However,
a critically-high temperature in the enclosure can cause hardware failure and compromise data integrity.
To prevent catastrophic data loss and further damage to components, the following conditions cause the
DS2500 to shut down:
A power supply removed from the enclosure
No operational blowers
An unacceptable temperature level in the enclosure
If any of these conditions exists, the EMU starts a timer to shut down the enclosure in 7 minutes. If the
condition is corrected before the 7 minute countdown is completed, the EMU aborts the shutdown
and normal operation resumes.
52
Troubleshooting
Page view 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 88 89

Comments to this Manuals

No comments