HP Modular Cooling System User Manual Page 62

  • Download
  • Add to my manuals
  • Print
  • Page
    / 83
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 61
Removal and replacement procedures 62
b.
Using a T-25 Torx driver, remove the four T-25 Torx screws at each corner that secure the water
group cover to the MCS G2 unit.
5. Remove the condensation pump ("Removing the condensation pump" on page 30).
6. Using a T-25 Torx driver, remove the two T-25 sheet metal screws securing the sensor bracket to the
MCS G2 unit (1).
7. Remove the sensor bracket and attached water level sensors from the MCS G2 unit (2).
8. Remove the cable ties and unwrap the cable harness.
9. Disconnect the water level sensor cables from the water controller.
Replacing the water level sensors
1. Connect the water level sensor cable to the water controller.
2. Align the sensor bracket to the appropriate holes in the MCS G2 unit (1).