Removal and replacement procedures 70
8.
Route the water valve cable through the back of the MCS G2 unit.
9. Connect the water valve cable to the appropriate connector on the water controller.
10. Wrap the insulation you previously removed around the water valve, and secure using either
electrical tape or a cable tie wrap.
11. Replace the sheet metal bulkhead.
a. Align the frame support to the appropriate holes in the MCS G2 unit.
b. Insert the two pieces of the frame into the MCS G2 unit, aligning them with the frame support.
i. Insert the left (return-side) piece of the frame, making sure it fits down around the large pipe.
(1)
ii. Insert the right (supply-side) piece of the frame, slightly overlapping the left (return-side) piece
of the frame. (2)