Removal and replacement procedures 61
Water level sensors
The water level sensors are a component of the water group located at the bottom of the MCS G2 unit.
The following tools are required for installation:
T-25 Torx driver
Removing the water level sensors
1. Disconnect the power ("Disconnecting the power" on page 23).
2. Remove the water controller ("Removing the water controller" on page 57).
3. Remove the bottom fan unit ("Removing the bottom fan unit" on page 29).
4. Remove the water group cover.
a. Using a T-25 Torx driver, remove the two flathead T-25 Torx screws that secure the condensation
pump.