HP Modular Cooling System User Manual Page 80

  • Download
  • Add to my manuals
  • Print
  • Page
    / 83
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 79
Specifications 80
Thermal and air flow performance
Maximum thermal and air flow
performance parameters
Single rack Dual rack
(Specification per rack)
Air temperatureinlet to rack-
mounted components
25ºC (68ºF) 25ºC (68ºF)
Chilled water temperature 15°C (45º57°F) 15°C (45º57°F)
Total rack-mounted component air
flow
2,600 cfm or less at 0 or more
pressure drop across the rack-
mounted components
1,300 cfm or less at 0 or more
pressure drop across the rack-
mounted components
Chilled water flow rate 15.5 gal/min (60 l/min) 7.9 gal/min (30 l/min)
Chilled water pressure differential at
flow needed to meet thermal
specifications
1.0 bar delta pressure 1.0 bar delta pressure
Heat lost to room Approximately 10% maximum
depending on the MCS settings
and room temperature
Approximately 10% maximum
depending on the MCS settings
and room temperature
Server heat load 35 kW maximum 17.5 kW maximum
Environmental specifications
Features Specifications
Operating temperature 5ºC to 35ºC (41ºF to 95ºF)
Non-operating temperature C to 60ºC (32ºF to 140ºF)
Transit temperature -30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours
Storage temperature -20ºC to 60ºC (-4ºF to 140ºF)
Operating humidity 20 to 80% relative humidity (non-condensing)
Non-operating humidity 5 to 95% relative humidity (non-condensing)
Operating altitude -76.2 to 3,048 m (-250 to 10,000 ft)
Non-operating altitude -76.2 to 9,144 m (-250 to 30,000 ft)
HP 10642 G2 Rack specifications
U height Width Depth Dynamic load (gross) Static load
42U 600 mm
(23.8 in)
1,000 mm
(39.4 in)
907.2 kg (2,000 lb) 1,360.8 kg (3,000
lb)