Page view 58
Environmental control system 59
Callout Sensor Quantity per
IT section
Description
1
Temperature and relative
humidity sensors
6
Monitor the temperature and humidity in the
six Adiabatic zones of the HP POD 240e NA
Report data to the AHU controllers
2
Differential pressure sensor
port
6
Works in combination with the AHU sensors to
monitor pressure in the six Adiabatic zones of
the HP POD 240e NA
Reports data to the AHU controllers
HVAC sensors
Six AHU temperature and pressure sensor probes work in combination with the differential pressure sensor
port, callout (2) in the figure above, to calculate the cooling unit discharge temperature and average pressure
in each IT section. This data is reported to the AHU controllers.
Top view shown
Hot aisle sensors
Top view shown