HP 240A User Manual Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 93
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
Life safety systems 22
Fire detection system
Each HP POD 240e NA is equipped with a fire alarm panel that is integrated with the fire detection system.
The fire system is designed as a stand-alone system, but the system can also interface with customer site fire
alarm systems. Customer site connections are the responsibility of the customer. Consult with HP for
connection locations.
The fire protection system includes:
VESDA air sampling smoke detection system (on page 22)
Manual fire pulls (on page 22)
Fire alarm panel (on page 23)
Fire alarm indicators (on page 23)
VESDA air sampling smoke detection system
CAUTION: Excess dust within the HP POD 240e NA can cause the VESDA smoke detector to
trigger a fire alarm.
The VESDA system features a single zone laser scan early warning smoke detector to provide the earliest
warning of a potential fire.
The orange VESDA piping that runs throughout the HP POD 240e NA includes inlets for smoke sampling. The
VESDA uses a high-efficiency aspirator to continuously draw in air from the HP POD 240e NA and circulate
the air through a dual-stage filter:
Stage 1A filter removes dust and dirt from the air sample.
Stage 2An ultra-fine filter removes remaining contaminants in the air sample.
After the air passes through the dual-stage filter, it enters a calibrated detection chamber where a laser scans
the air sample for the presence of smoke. The VESDA system cycles through two levels if smoke is detected:
Level 1Smoke concentration reaches the first setpoint, and the VESDA system sends an alarm signal
indicating that a fire might exist.
Level 2Smoke concentration reaches the second setpoint, and the VESDA system indicates that a fire
exists in the HP POD 240e NA.
IMPORTANT: The VESDA filter must be changed regularly to be sure that smoke detection
readings are accurate. For more information about changing the VESDA filters, see the HP
Performance Optimized Datacenter 240e NA Maintenance and Service Guide.
Manual fire pulls
The HP POD 240e NA has six fire pulls; two in each aisle. They are located in the life safety switch cabinet
next to each personnel door of the HP POD 240e NA.
Manually activating a fire pull does the following:
Triggers a fire alarm
Activates the fire alarm system horn and strobe lights
Page view 21