Specifications 75
Fire alarm panel connections
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP
POD 20c.
Water specifications
The following table describes the chilled water system specifications for the HP POD 20c.
Feature Specification
Facility input temperature to the HP POD
20c
12º to 24ºC (55º to 75ºF)
Max design pressure
1,034 kPa (150 psi)
HP POD 20c pressure drop
172.4 kPa (25 psi)
HP POD 20c water flow rate
454 lpm (120 gpm*)
Chilled water supply and return
connections
Two DIN PN16 DN80 flanges
*Measurement is in US gallons per minute.
Rack specifications
Standard HP POD 20c racks (AT978A)
Feature Specification
U height
50U
Width
54.6 cm (21.5 in)
Depth
99 cm (39 in)*
Maximum load weight
1,360.7 kg (3,000 lb)
*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement.
Thermal and air flow performance
Maximum thermal and air flow
performance parameters
HP POD 20c specification
Air temperatureInlet to
rack-mounted components
Dependent on IT configuration and
chilled water inlet temperature
Chilled water temperature
12°C to 24°C (55°F to 75°F)
Total rack-mounted component air
flow
Variable as required to maintain hot
aisle setpoint temperature and
dependent on IT configuration
Heat rejection capacity
300 kW
Environmental specifications
Feature Specification
Operating temperature
-28ºC to 54ºC (-18ºF to 130ºF)
Non-operating temperature*
-29ºC to 54ºC (-20ºF to 130ºF)