Specifications 74
Specifications
General HP POD 20c specifications
Features Specifications
Overall dimensions
Height—3.05 m (10 ft)
Length—6.10 m (20 ft)
Width2.43 m (7.97 ft)
Weight
1
Empty7,711 kg (17,000 lb)
Maximum fully loaded22,680 kg (50,000 lb)
Maximum power
2
288 kW
Power input voltage
380-415 V, 3-phase, 4-wire
Power input current
2 x 320 A electrical busways 3-phase, 4-wire feeders
Maximum rack quantity
10 racks
Rack Units (RU) per rack
50 RU
Rack Units (RU) total
500 RU
Average capacity per rack (kW)
30 kW
Peak rack capacity
69 kW
Voltage to rack
200-240 VAC
Minimum quantity of PDUs per HP POD 20c
10 (one per rack)
Maximum quantity of PDUs per HP POD 20c
20 (two per rack)
Maximum power per PDU
30A = 17 kW; 60A = 34 kW
Network supported
Bulk cable pass-through-fiber
Bulk cable pass-through-copper
External rated DEMARC box
1
The empty weight includes the HP POD 20c structure, empty racks, PDUs, and drop boxes. It does not include IT
equipment.
2
The maximum power depends on the exact installation and power configuration in your POD. The HP POD 20c is
electrically limited to 288 kW.
Electrical specifications
Electrical busway system information
Feature Specification
Number of busways
2
Frequency
50-60 Hz
Amps (per busway)
200 A
Voltage (per busway)
380-415 VAC Wye
Grounding
Copper
Busway configuration
3-phase + neutral + equipment ground