Chapter 5 - Parameter List
5-15
Keypad Display Setting Range
Code Description
LCD 7-Segment LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
Main-drive 17
Analog hold 18
XCEL stop 19
P Gain2 20
SEQ-L 21
SEQ-M 22
SEQ-H 23
Manual 24
Go step 25
Hold step 26
Trv Off.Lo 27
Trv Off.Hi 28
Interlock1 29
Interlock2 30
Interlock3 31
Interlock4 32
Pre excite 33
Spd/Trq 34
ASR P/PI 35
EXT-03
Multi-Function Input
Terminal ‘P5’ Define
P5 define
03 - XCEL-M Yes
EXT-04
Multi-Function Input
Terminal ‘P6’ Define
P6 define
04
Same as Above
- XCEL-H Yes
6-2
None 0
Override 1
EXT-05 V2 Mode Selection
V2 mode
05
Reference 2
- None No 6-2
EXT-06
Filtering Time Constant
for V2 Input Signal
V2 filter
06 0 to 10000 [ms] 1 10 [ms] Yes
EXT-07
V2 Input Minimum
Voltage
V2 volt x1
07 0 to 10 [V] 0.01 0.00 [V] Yes
EXT-08
Frequency
Corresponding to V2
Input Minimum Voltage
V2 freq y1
08 0 to FU1-20 0.01 0.00 [Hz] Yes
EXT-09
V2 Input Maximum
Voltage
V2 volt x2
09 0 to 10 [V] 0.01 10.00 [V] Yes
EXT-10
Frequency
Corresponding to V2
Input Maximum Voltage
V2 freq y2
10 0 to FU1-20 0.01 60.00 [Hz] Yes
6-2
None 0
Feed-back 1
EXT-12
Usage of Pulse Input
Signal
F mode
12
Reference 2
- None No 6-2
Reverse 1
EXT-13 Real Speed Direction
RealSpdDir
13
Forward 2
- - -