HP Modular Cooling System User Manual Page 62

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 61
Specifications 62
Thermal and air flow performance
Maximum thermal and air flow performance
parameters
Specifications
Air temperature—inlet to rack-mounted components 25ºC (68ºF)
Chilled water temperature 7º–10°C (45º–50°F)
Total rack-mounted component air flow 2,600 cfm or less at 0 or more pressure drop
across the rack-mounted components
Chilled water flow rate 21 gal/min
Chilled water pressure differential at flow needed to
meet thermal specifications
2.0 bar delta pressure
Heat lost to room approximately 10% maximum depending on
the MCS settings and room temperature
Heat transferred to cooling fluid 35 kW maximum
Environmental specifications
Features Specifications
Operating temperature 5ºC to 52ºC (41ºF to 95ºF)
Non-operating temperature 0ºC to 60ºC (32ºF to 140ºF)
Transit temperature -30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours
Storage temperature -20ºC to 60ºC (-4ºF to 140ºF)
Operating humidity 20 to 80% relative humidity (non-condensing)
Non-operating humidity 5 to 95% relative humidity (non-condensing)
Operating altitude -76.2 to 3,048 m (-250 to 10,000 ft)
Non-operating altitude -76.2 to 9,144 m (-250 to 30,000 ft)
HP 10642 G2 Rack specifications
U height Width Depth Dynamic load (gross) Static load
42U 600 mm
(23.82 in)
1,000 mm
(39.37 in)
907.18 kg (2,000 lb) 907.18 kg (2,000
lb)