Installation 10
Counter hold wrench (included with your MCS kit contents)
Bubble level
Installing the MCS unit
WARNING: The MCS unit and rack are shipped together on a heavy duty shock pallet
weighing approximately 2000 lb. HP recommends hiring professional movers to move the
heavy duty shock pallet, and then remove the MCS unit and rack from the pallet and into to the
final location.
CAUTION: Contaminated water may cause decreased cooling capacity or disruption in
service. It is important that the water flowing into the MCS unit meets the guidelines stated in
the HP Modular Cooling System Site Preparation Guide. Damage caused by contaminated
water is not covered by the MCS unit warranty.
IMPORTANT: You must read the HP Modular Cooling System Site Preparation Guide before
beginning the installation process.
IMPORTANT: Be sure to install the HP Water Hook-up Option Kit before connecting the In and
Out water hoses to the water lines.
1. Read the unpacking instructions on the MCS packaging material.
2. With four or more people, carefully remove the MCS unit and rack from the pallet.
3. Roll the MCS unit and rack approximately 91 cm (3 ft) in front of the final location.
4. Loosen the jam nut, and raise the unit by lowering the two rear leveling feet on both the MCS unit
and the rack until the rear caster plate can be removed.