HP Moonshot 1500 Chassis User Manual Page 21

  • Download
  • Add to my manuals
  • Print
  • Page
    / 189
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 20
Example 4 Output from sdr list all command
ZoMC | Static MC @ 20h | ok
254 | Log FRU @FEh f0.60 | ok
IPMB0 Phys Link | 0x00 | ok
ChasMgmtCtlr1 | Static MC @ 44h | ok
PsMgmtCtlr1 | Dynamic MC @ 52h | ok
PsMgmtCtlr2 | Dynamic MC @ 54h | ok
PsMgmtCtlr3 | Dynamic MC @ 56h | ok
PsMgmtCtlr4 | Dynamic MC @ 58h | ok
CaMC | Dynamic MC @ A6h | ok
CaMC | Dynamic MC @ A8h | ok
CaMC | Dynamic MC @ AAh | ok
CaMC | Dynamic MC @ ACh | ok
CaMC | Dynamic MC @ AEh | ok.
.
.
.
CaMC | Dynamic MC @ A4h | ok
Example 5 Output from sdr list all command at cartridge
01-Front Ambient | 21 degrees C | ok
02-CPU | 40 degrees C | ok
03-DIMM | 25 degrees C | ok
04-Cart Ctrlr | 24 degrees C | ok
05-CPU Zone | 29 degrees C | ok
06-LOM Zone | 36 degrees C | ok
CaMC | Dynamic MC @ A4h | ok
SnMC | Dynamic MC @ 72h | ok
SnMC 1 | Log FRU @01h c1.62 | ok
See “Verbose output examples” (page 164) for an example of verbose output from the sdr list
all command.
Events
Events are special messages sent by the management controller when they detect system
management events. Some examples of events are temperature threshold exceeded, voltage
threshold exceed, correctable ECC memory error, etc. These events are processed and usually
logged in the SEL. This is similar to the SDR in that it provides a centralized non-volatile storage
area for platform events that are logged autonomously by the MC or directly with event messages
sent from the host.
There is an abundance of information available from an event log entry. By default IPMItool displays
only the basic data for the event and the sensor that triggered it. Detailed information is available
with the verbose option.
Example 6 Output from sel list command
0 | 04/16/2013 | 20:22:01 | Power Supply #0x04 | Failure detected | Asserted
1 | 06/28/2013 | 20:36:17 | Power Supply #0x02 | Presence detected | Deasserted
2 | 07/28/2013 | 00:20:52 | Power Supply #0x02 | Failure detected | Asserted
3 | 08/04/2013 | 00:23:10 | Power Supply #0x02 | Presence detected | Deasserted
4 | 08/09/2013 | 14:34:48 | Fan #0x07 | Transition to Off Line | Asserted
5 | 08/09/2013 | 14:34:49 | Fan #0x07 | Transition to Running | Deasserted
See “Verbose output examples” (page 164) for an example of verbose output from the sel list
command.
Events 21
Page view 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 188 189

Comments to this Manuals

No comments