(Optional) Sensor Base Stations 60
2.
Set the device unit ID to a number value between 1 and 32. If multiple meters are connected in a daisy
chain series, each meter must have a unique device unit ID.
NOTE: The baud rate you set on the ION Energy Meter Modbus ID ("Programming the Modbus
ID" on page 59) must match the baud rate you set in the Modbus Base Station configuration
("Configuring the Modbus Base Station" on page 61).
3. Set the serial baud rate to 19.2K.