Power Connector
FIGURE 6
AC Power Connector Location
Electrical Requirements
AC Site Requirements
Overcurrent protection devices are required for each cabinet where the disk system is
installed. They must be positioned between the power source and the disk system.
These protective devices must not trip when exposed to an inrush current of 30 amps
lasting 5 ms.
I
Note These protection devices must meet all applicable electrical safety
requirements and be approved for the intended purpose.
TABLE 3 AC Power Requirements
Electrical Element Requirements
Voltage 100-240 VAC
Frequency 50-60 Hz
Input Current < 1 amp
Maximum Surge Current 30 amps peak