Operator display 47
Indicators Meaning
Sensors HEX1, HEX2, or HEX3 sensors (this is the water to air heat exchanger unit
temperature of the intake to the servers)
SNMP notification Warning
Type of message Warning
Solution:
1. Remove the fan unit.
2. Remove the HEX unit.
3. Reinstall the same HEX unit.
4. Reinstall the same fan unit.
If the warning message does not clear after the module is reseated, replace the HEX unit with a CSR part.
For more information on CSR parts, see "Replaceable parts and maintenance and service information (on
page 63)."
HEX temperature out failed (Server Exhaust Temperature failed)
Indicators Meaning
Actual operator display alarm
message
FAN1, FAN2, or FAN3 Temp. Out Failed
Actual web interface alarm
message
Top Fan Exhaust Air Temperature Sensor from Server Failed
Condition Temperature reading is beyond limit (possible open circuit)
Sensors FAN1, FAN2, or FAN3 sensors (this is the fan unit temperature of the
exhaust from the servers)
SNMP notification Warning
Type of message Warning
Solution:
1. Remove the fan unit.
2. Reinstall the same fan unit.
If the warning message does not clear after the module is reseated, replace the fan unit with a CSR part.
For more information on CSR parts, see "Replaceable parts and maintenance and service information (on
page 63)."
Air temperature sensor failed
Indicators Meaning
Actual operator display alarm
message
Air Temp. Sens Failed
Actual web interface alarm
message
Air Temperature Sensor Failed
Condition Single air temperature sensor is significantly different from the others
Sensors Air temperature sensors
SNMP notification Warning
Type of message Warning