3-phase 5-wire input
Option 6:
3-phase 4-wire input
44 A 44 A 44 A
Required Power Receptacle-
Options 6 and 7
None. Cord, plug and included. Receptacle should be ordered separately. Electrician must
hard wire receptacle to site power.
Maximum Input Power (watts)
8,490 12,196 24,392
Typical Input Power (watts)
5,900
4 cells, 32 GB, 4 I/O chassis
with 6 PCI each
9,800
8 cells, 32 GB, 4 I/O chassis
with 6 PCI each
19,600
16 cells, 32 GB, 4 I/O
chassis with 6 PCI each
Environmental Characteristics
Environmental CharacteristicsEnvironmental Characteristics
Environmental Characteristics
Acoustics
65 dB
Operating temperature
68° to 86°F (20°C to 30°C)
Non-operating temperature
-40° to 158°F (-40° to 70°C)
Maximum rate of temperature
change
68°F/hr (20°C/hr)
Operating relative humidity
15% to 80% @ 86°F (30°C)
Operating altitude
0 to 10,000 ft (0 to 3.1 km)
Non-operating altitude
0 to 15,000 ft (0 to 4.6 km)
Regulatory Compliance
Regulatory ComplianceRegulatory Compliance
Regulatory Compliance
Safety
IEC 950:1991+A1, +A2, +A3, +A4;
EN60950:1992+A1, +A2, +A3, +A4, +A11;
UL 1950, 3rd edition;
cUL CSA C22.2 No. 950 95
Key Dates
Key DatesKey Dates
Key Dates
First CPL date
6/03
First ship date
3Q03
Dimensions
DimensionsDimensions
Dimensions
Height
5.25 ft or 6.43 ft (1.6 meters or 1.96 meters)
Depth
45.5 in (115.67 cm)(same depth as 32W)
Width
24.0 in (60.96 cm)
Electrical Characteristics
Electrical CharacteristicsElectrical Characteristics
Electrical Characteristics
AC input power
200-240 VAC, 50/60 Hz
Current requirements at
200V240V
16 A
Typical maximum power
dissipation (watts)
2290
Maximum power dissipation
(watts)
3200
Environmental Characteristics
Same as Superdome
QuickSpecs
HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,
and 64-way
and 64-wayand 64-way
and 64-way
TechSpecs
DA - 11717 Worldwide — Version 1 — June 30, 2003
Page 33
Page view 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 39

Comments to this Manuals

No comments