Table 5 T-Class Storage System Power Requirements (continued)
160208BTUs/hour
4 x 450 GB FC Drive Magazines
5788Watts
194300BTUs/hour
4 x 600 GB FC Drive Magazines
6573Watts
222249BTUs/hour
4 x 1 TB NL Drive Magazines
3247Watts
109160BTUs/hour
4 x 2 TB NL SATA Drive Magazines
3242Watts
111143BTUs/hour
Service Processor
260SuperMicro Watts
1370 BTUs/hr.SuperMicro
BTUs/hour (fully
populated)
280SuperMicro II Watts
955 BTUs/hr.Supermicro II
BTUs/hour (fully
populated)
1
Theoretical maximum based on branch circuit capacity.
2
Under maximum load.
3
Up to 10 drive magazines (40 drives) per drive chassis.
NOTE: All calculations in Table 5 (page 10) are based on fully populated components; for
example, a fully populated drive chassis contains 40 disks. Specifications are not provided for
partially populated drive chassis because different drives and magazine types have varying current
requirements and can be installed in a variety of different combinations. Therefore, only the
maximum, fully loaded configuration is cited.
NOTE: The total system peak inrush current on system startup can vary depending on the system
configuration but is mitigated through a staggered (sequenced) drive spin-up and by distributing
the load equally unless there is a failure on a given line.
Environmental Specifications
The following table lists the environmental specifications for the T-Class Storage systems.
Table 6 Environmental Specifications for HP 3PAR Storage systems
ValueSpecification
0 –10,000 ft (3,048 m) 0 –40,000 ft (12,192 m)Altitude Operating Non-operating
50 –104° F (10–40° C)
Ambient temperature
Operating
Environmental Specifications 11