HP UPS R7000 User Guide Abstract This document includes installation, configuration, and operation information for the HP UPS R7000. This document i
Component identification 10 ERM rear panel Item Description 1 ERM input connector for the small plug on the split ERM cable of another ERM outp
Installation and configuration 11 Installation and configuration Precautions Save these instructions. This document contains important safety instru
Installation and configuration 12 • Hex nuts • Cage nuts • Cage nut-fitting tool Selecting a site WARNING: To prevent fire or electric shock
Installation and configuration 13 WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that: • The leveling feet ar
Installation and configuration 14 3. Install clip nuts into the rear of the rack. 4. Insert screws through the mounting rail into the clip nuts.
Installation and configuration 15 5. Install the rail reinforcement plates and tighten using hex nuts with captive washers included in the kit, inst
Installation and configuration 16 7. Install the rear mounting brackets using hex nuts. Wait until the unit is installed and the brackets are adjust
Installation and configuration 17 Installing the UPS Before installing the UPS, review and observe all warnings in "Precautions (on page 11).&q
Installation and configuration 18 Attaching the UPS front bezel Connecting the serial communications port CAUTION: Use only the computer i
Installation and configuration 19 Configuring a USB to serial converter NOTE: This procedure was tested on the Windows® XP Professional, Wi
© Copyright 2011, 2013 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warr
Installation and configuration 20 o Bits per second: 9600 o Data Bits: 8 o Parity: None o Stop bits: 1 o Flow control: None 9. Click Advanced.
Installation and configuration 21 b. Click Scan for hardware changes to refresh the screen and display the changes. Connecting the USB communicatio
Installation and configuration 22 NOTE: Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or equivalent). Separate
Installation and configuration 23 For information about verifying the REPO connection, see "Verifying the REPO port connection (on page 33)&quo
Installation and configuration 24 This connection is used to access the UPS Network Module remotely through the web interface. The UPS Network Modul
Installation and configuration 25 Connecting the UPS cord retention clips Charging the UPS batteries With the UPS in Standby mode, allow the batte
Installation and configuration 26 2. Connect the RJ-45 connector on the DB-9 to RJ-45 cable to the Settings/AUX connector on the UPS Network Module.
Installation and configuration 27 2. At the prompt, enter admin. The HP UPS Network Module Configuration Menu appears. Use the HP UPS Network Module
Installation and configuration 28 5. Click Sign In. The HP UPS Network Module web interface appears. Configuring the UPS Network Module settings U
Installation and configuration 29 3. Install the mounting ears on the chassis using the screws provided. 4. With one person on each side, lift the
Contents 3 Contents Overview ...
Installation and configuration 30 Connecting the ERM to the UPS Connect both ends of the split ERM cable to the ERM connectors on the UPS rear panel
UPS operations 31 UPS operations Modes of operation The UPS has three modes of operation: • Standby mode (on page 31) • Operate mode (on page 31)
UPS operations 32 • Over temperature • Output short • Hardware failure Transferring the UPS between modes To transfer between Operate mode and B
UPS operations 33 Main menu Submenu Display information or menu function — Battery status Battery Charging/Floating/Resting, Charge Level, ERM Nu
UPS operations 34 1. Initiate a REPO by closing the REPO contact. CAUTION: If the polarity is reversed while connecting the REPO port, the UPS p
Power management 35 Power management Power Protector software HP Power Protector software ensures maximum power reliability of computer systems thro
Power management 36 • Delays reboot by load segment after a power outage to sequence the startup of system components.
Maintenance 37 Maintenance Removing the UPS front bezel Removing the ERM front bezel Replacing the UPS Network Module This component is hot-swap
Maintenance 38 1. (optional) To replace the component with the UPS powered down, refer to "Powering down the UPS (on page 34)." 2. Disco
Maintenance 39 WARNING: To prevent personal injury, prepare the area and observe all materials-handling procedures when transporting a battery
Contents 4 Operate mode ...
Maintenance 40 2. Disconnect the battery leads. 3. Remove the UPS battery bracket. 4. Remove the UPS battery modules. IMPORTANT: Do not pull
Maintenance 41 To replace the component, reverse the removal procedure. IMPORTANT: Charge the batteries for at least 24 hours before supplyin
Maintenance 42 6. Disconnect the battery leads. 7. Remove the UPS battery bracket.
Maintenance 43 8. Remove the UPS battery modules. 9. Remove the screws securing the UPS to the rack. 10. Remove the UPS from the rack. To replace
Troubleshooting 44 Troubleshooting Alarm troubleshooting This UPS is designed for durable, automatic operation and also to alert you whenever potent
Troubleshooting 45 Alarm number Alarm name Alarm description Alarm type 59 Utility Not Present The utility level has fallen below the Utility No
Troubleshooting 46 Silencing an audible alarm To silence an alarm, press any button on the front panel display to silence the alarm. If the alarm st
Troubleshooting 47 c. Wait at least 5 seconds and restart the UPS. d. If the condition persists, verify that the load devices are not defective. 4.
Troubleshooting 48 Action: Remove one or more load devices to reduce the power requirements.The UPS continues to operate, but might switch to Auto-B
Troubleshooting 49 UPS is in Auto-Bypass mode Action: 1. If power management software is being used, check the log files to obtain specific error i
Contents 5 Minimum battery runtime ...
Specifications 50 Specifications UPS physical specifications Parameter Value Height 17.1 cm (6.75 in) Depth 73.4 cm (28.9 in) Width 43.7 cm (17.
Specifications 51 UPS model Load segment Circuit breaker Output receptacles Maximum current 1 x L6-30R Up to full UPS power rating 2 20 A¹
Specifications 52 Feature Specification Voltage wave shape Sine wave; 5% THD with typical PFC load Surge suppression High-energy 6500 A peak Noise
Specifications 53 Environmental specifications Feature Specification Operating temperature 10°C to 40°C (50°F to 104°F); UL-tested at 25°C (77°F
Spares 54 Spares Ordering spares To order a spare, visit the HP website (http://www.hp.com/buy/parts). To replace parts under warranty, contact an H
Regulatory information 55 Regulatory information Safety and regulatory compliance For safety, environmental, and regulatory information, see Safety
Regulatory information 56 • The UPS is plugged into a suitably grounded and wired outlet using no extension cords, adapters, other ground wires, or
Electrostatic discharge 57 Electrostatic discharge Preventing electrostatic discharge To prevent damaging the system, be aware of the precautions yo
Support and other resources 58 Support and other resources Before you contact HP Be sure to have the following information available before you call
Acronyms and abbreviations 59 Acronyms and abbreviations ERM extended runtime module IEC International Electrotechnical Commission PDU power distr
Overview 6 Overview UPS R7000 overview The HP UPS R7000 features a 4U rackmount design and offers power protection for loads up to 7200 VA/7200 W (N
Documentation feedback 60 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat
Index 61 A authorized reseller 58 B backup time, insufficient 48 batteries, care and storage 39 batteries, charging 25, 30 batteries, replac
Index 62 overview, UPS 6 P phone numbers 58 power management 35 power protection specifications 50 preparation procedures 11 problem diagn
Component identification 7 Component identification UPS front panel Item Description 1 LCD display 2 Control buttons 3 Battery compartment U
Component identification 8 Item Component Description 2 Up arrow Scroll through the menu structure 3 Down arrow Scroll through the menu structur
Component identification 9 Item Description 13 Load segment 2 (3) C19 receptacles 14 Load segment 2 circuit breaker (controls the C19 receptacles,