Chapter 1 Preparation for Cabling the HP NetServer LXr85005If you install several HP NetServers on one circuit, however, precautions arenecessary. For
Chapter 1 Preparation for Cabling the HP NetServer LXr85006Prevent Electrical ShockWARNING Ensure site electrical circuits have reliable earth groundi
Chapter 1 Preparation for Cabling the HP NetServer LXr85007Generic Rack Assembly StepsSuggested Method for Building an HP NetServer Rack Installation1
Chapter 1 Preparation for Cabling the HP NetServer LXr850083. Prepare Rack Enclosures for AssemblyWARNING A tip-over hazard exists. Rack enclosures a
Chapter 1 Preparation for Cabling the HP NetServer LXr85009WARNING When equipment is mounted on slidies, a tip-over hazardexists. Always take the prec
Chapter 1 Preparation for Cabling the HP NetServer LXr850010NOTE Older HP Systems racks may require that enclosures to be tiedtogether before any comp
Chapter 1 Preparation for Cabling the HP NetServer LXr8500113. Install the Redundant Switch, if you have one, in one of the configurationsshown in App
Chapter 1 Preparation for Cabling the HP NetServer LXr850012NOTE For both safety and accessibility, always start assembly at thebottom of the rack and
Chapter 1 Preparation for Cabling the HP NetServer LXr850013• Determine configurations for and mount the PDU (Power Distribution Unitor Units).
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
HP NetServer LXr 8500Rack Assembly and CablingReference GuideHP Part Number D7054-90015Printed September 1999Artisan Technology Group - Quality Instru
152 Rack Cabling ReferencesRack Configuration ToolsSelected reference material derived from HP’s rack configuration tools ispublished in this chapter
Chapter 2 Rack Cabling References16◊ available in either 208 VAC or 230/240 VAC configurations forinternational markets◊ Uninterruptible Power Supply
Chapter 2 Rack Cabling References17Table 2-2. LXr 8500 Plugs and Receptacles Reference208 VAC Mains 230/240V MainsLXr 8500 Jumper CordincludedC19 to C
Chapter 2 Rack Cabling References18Power Distribution UnitsTwo types of Power Distribution Units (PDU) are currently available for the LXr8500, as fol
Chapter 2 Rack Cabling References19Table 2-3. PDU Placement is not Recommended behind These UnitsHP Product NameCan PDU Be MountedBehind?ReasonHP NetS
Chapter 2 Rack Cabling References20The 200/240 VAC, wide-range Power Distribution Unit (PDU) can be mounted inseveral configurations with the LXr 8500
Chapter 2 Rack Cabling References21Guidelines for Powering the LXr in a RackWide Ranging PDU ConfigurationsUse of four possible 200/240 VAC PDU config
Chapter 2 Rack Cabling References22amp PDU may not provide sufficient receptacles. In this case, use theY-cable to connect HP Rack Storage/8 or Rack S
Chapter 2 Rack Cabling References23Table 2-6. 208 VAC Power and Current:Approximate Requirements of Rack Optimized Devices and ComponentsDevice (Note
Chapter 2 Rack Cabling References24Table 2-7. 230/240 VAC Power and Current:Approximate Requirements of Rack Optimized Devices and ComponentsDevice (
iiNoticeThe information contained in this document is subject to change without notice.Hewlett-Packard makes no warranty of any kind with regard to th
Chapter 2 Rack Cabling References25Data Cabling References and GuidelinesA series of positioning rules is used in the HP rack configuration tools to h
Chapter 2 Rack Cabling References26• Ensure the monitor cables and mouse cables are long enough to allow theNetServer to be extended at the same time
273 Procedure for Connecting andRouting Cables to the LXr 8500Step 1: Prepare to Cable the HP NetServer LXr8500Assess How Components Will be Connected
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850028Mount Power Distribution UnitsPlan the location of the Power Distribution Unit
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850029Rack Storage/12Single Bus Configured StorageDashed Lines Indicate Dual Bus Conf
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850030HP NetServer Lxr 8500HP Rack Storage/12FC with GBICsHP Rack Storage/8HP Rack St
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850031Figure 3-3. Connecting the Data Cables between the LXr 8500and Rack Storage/12F
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850032and monitor for more than one server, attach the cables for the HP ConsoleSwitc
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850033loaded rack, see the section of this chapter entitled "Determining andBala
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850034Location ofReceptaclesfor JumperCables fora TypicalRackMonitorNote PDUVerticall
iiiContents1 Preparation for Cabling the NetServer LXr 8500... 1About Cabling the LXr 8500...
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850035Alternate 208 VAC Power ConfigurationsIn the 208 VAC case, without a UPS, make
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850036Jumper CablesSupplied withMass StorageUnits Jumper CableSupplied with NetS
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850037230/240V PDU Rack Power ConfigurationsConfigurations for the 230/240 VAC, PDU o
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850038Table 3-2. 230/240 VAC PDU Power and CurrentComponent1ModelPower(VA)Power(W)Cur
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850039Jumper CableSupplied withNetServerJumper CablesSupplied with Mass St
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850040shows two LXr 8500 units powered by two PDUs and two UPS units. Pluggingeach UP
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850041High Density ConfigurationHigh Density Configuration ExampleA high density conf
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850042Step 4: Managing and Routing CablesUsing the Cable Management Arm and the Cable
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850043B. Plug power and data cables into the back of the ServerF. Drape cables throu
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850044WARNING Before sliding the HP NetServer LXr 8500 out of the rack,make sure you
ContentsivOverview of LXr 8500 Data Connections... 28Attach Data Cables to the Server...
Chapter 3 Procedure for Connecting and Routing Cables to the LXr 850045bind, adjust as necessary. Repeat until the Cable Management Arm extendsand ret
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
47A Cabling ChecklistChecklist for Cabling ProcessUse the Site Preparation Checklist in Chapter 1 to make sure your site is ready.Read and follow all
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
49B Considerations in Mounting theRedundant SwitchTable B-1 shows the Redundant Switch in four possible configurations.The illustrations which follow
Appendix B Considerations in Mounting the Redundant Switch50Table B -1. Components for Use with the Redundant Switch and the LXr 8500North America: 20
Appendix B Considerations in Mounting the Redundant Switch51SKU 045-1SwitchCaptive Cords, with L6-20P Cord EndsCaptive UPS Cord with L6-20P connects t
Appendix B Considerations in Mounting the Redundant Switch52Note that switches of 230/240 VAC can be mounted in the same way as the 208VAC models show
53IndexAair flow in the rack, 26CCable Guideensure installed, 27cable managementensure the the Cable Guide is inplace, 27mount the Cable Management Ar
Index54208 VAC, LXr 8500 configuration,34208/240 VAC, 10 amp extension, 18208/240 VAC, 16 amp, 18230/240 VAC illustration, 37, 39configuration guideli
11 Preparation for Cabling theNetServer LXr 8500About Cabling the LXr 8500NOTE A checklist for the cabling process is included in Appendix A.Before Yo
Index55UPS or uninterruptible power supplyunterminated power cord for, 5Vvoltage optionsplugs and receptacles, 16Wwide ranging switchless power units,
Artisan Technology Group is your source for quality new and certied-used/pre-owned equipment• FAST SHIPPING AND DELIVERY• TENS OF THOUSANDS OF IN-S
Chapter 1 Preparation for Cabling the HP NetServer LXr85002Figure 1-1. The HP NetServer LXr 8500Site PreparationYou may want to copy and use the site
Chapter 1 Preparation for Cabling the HP NetServer LXr85003Site Preparation ChecklistTable 1-1. Site Preparation ChecklistHP NetServer General Guideli
Chapter 1 Preparation for Cabling the HP NetServer LXr85004Table 1-1. Site Preparation Checklist (Continued)Environment and Space RequirementsMust mee