Confirm that the resistance between the chassis and the ground is less than 1 ohm.
Site requirements
The router can only be used indoors.
This section provides information about temperature, humidity, cleanness, and air quality requirements,
as well as rack-mounting requirements and protection against damage from lightning and EMI.
Table 2 Temperature and humidity requirements
Tem
p
erature Relative humidit
y
0°C to 40°C (32°F to 104°F) 5% to 90%
Table 3 Dust concentration limit in the equipment room
Substance Concentration limit (
p
articles/m
3
)
Dust particles 3 x 10
4
(No visible dust on desk in three days)
NOTE:
Dust particle diameter 5 μm
Table 4 Harmful gas concentration limits
Gas Max. (m
/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
To prevent overheating:
Provide adequate clearance for air flow, including at least 10 cm (3.94 in) ventilation space around
the router's air intake and outlet vents.
Make sure the site has an adequate cooling system.
ESD prevention
To prevent the electronic components from being damaged by ESD, follow these guidelines:
The equipment and floor are correctly grounded.
The equipment room is dust-controlled.
Wear an ESD wrist strap when inspecting or handling a circuit board.
To attach an ESD wrist strap:
1. Wear the wrist strap on your wrist.
No wrist strap is supplied with the router. Prepare it yourself.
2. Lock the wrist strap tight around your wrist to keep good contact with the skin.
3. Insert the ESD plug into the ESD socket in the chassis.