506 01 5102 00 March 2008INSTALLATION INSTRUCTIONS3-Phase R-410A Split System Heat PumpProduct Family: H4H3These instructions must be read and under
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump10 506 01 5102 00Figure 11 Typical Thermostat (Control Circuit) ConnectionsLEGEND24-V
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump506 01 5102 00 11DEFROST SYSTEMA. DEFROST THERMOSTATThe defrost thermostat is factory i
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump12 506 01 5102 00START-UP PROCEDURE1. Set indoor thermostat selector switch to OFF.2. T
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump506 01 5102 00 13Figure 14 R-410A Required Liquid Line Temperature (°F) - Cooling ModeM
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump14 506 01 5102 00TROUBLESHOOTINGSome models are factory equipped with the ComfortAlertt
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump506 01 5102 00 15Figure 16 Comfort Alertt Diagnostics (some models)Status LED Status LE
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump16 506 01 5102 00Figure 17 Comfort Alertt Diagnostics (some models)Miswired Module Indi
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump2 506 01 5102 00INSPECT NEW UNITAfter uncrating unit, inspect thoroughly for hiddendama
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump506 01 5102 00 3Figure 1 Clearances (various examples)Wall6”24”ServiceWallWallWall6”6”P
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump4 506 01 5102 00UNIT SUPPORTNOTE: Unit must be level 2 degrees ( inch rise or fallpe
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump506 01 5102 00 5REFRIGERATION SYSTEMA. COMPONENT MATCHESCheck to see that the proper sy
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump6 506 01 5102 00transmission between the tubing and the foundation orwall.Along floor o
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump506 01 5102 00 7F. SERVICE VALVESService valves are closed and plugged from the factory
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump8 506 01 5102 00Figure 7Deep Vacuum Gauge Responseand System Conditions500MINUTES012461
INSTALLATION INSTRUCTIONS 3-phase R-410A Split System Heat Pump506 01 5102 00 9ELECTRICAL WIRING!WARNINGELECTRICAL SHOCK HAZARDFailure to follow this