HP POD specifications 11
External hot aisle view
Water supply specifications
Feature Specification
Facility input temperature to HP POD 12º to 24ºC (55º to 75ºF)
Working pressure 1034 kPa (150 psi)
HP POD pressure drop 1732 kPa (25 psi)
HP POD water flow rate 908.5 l/min (240 gal/min)
Cooling water supply and return
connections
Two 10.16 cm (4 in)
ANSI/ASME 150# flanges
Humidifier
See the humidifier manual for
exact humidifier requirements