HP XP1024 Owner's Manual Page 43

  • Download
  • Add to my manuals
  • Print
  • Page
    / 124
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 42
XP128 hardware 43
Table 9 (page 43) lists the basic AC power requirements for three-phase
operation of the XP128 DKC.
Table 8. 30-Amp, 50 or 60 Hz, Single-Phase DKC Operation
Parameter
Nominal Rated Voltage (VAC)
200 208* 220 230 240
Rated line current per
power cord (Arms)
10.2 9.5 9.4 9.0 8.7
Number of power cords 4 4 4 4 4
Number of circuit breakers 4 4 4 4 4
Recommended circuit
breakers
30A 30A 30A 30A 30A
* 60 Hz only.
Table 9. 30-Amp, 50 or 60 Hz, Three-Phase DKU Operation
Parameter
Nominal Rated Voltage (VAC)
200 208
*
220 230 240 380 400 415
Rated line current per
power cord (Arms)
11.1 10.7 10.0 9.6 9.1 6.0 5.5 5.3
Number of power
cords
2 2 2 2 2 2 2 2
Number of circuit
breakers
2 2 2 2 2 2 2 2
Recommended
circuit breakers
30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
* 60 Hz only.