HP Performance Optimized Datacenter 20c Site Preparation and Requirements Guide—International Abstract This document provides site preparation guida

Page 2

Site requirements 10 Side view clearances shown Top view for multiple POD installation minimum clearances shown Adequate space around the HP POD 2

Page 3 - Contents

Site requirements 11 Grounding requirements The HP POD 20c structure and internal components are all bonded together. A common grounding electrode c

Page 4 - Contents 4

Site requirements 12 Front view shown Utilities Consider the proximity to required utilities, such as power, water, and network connections. While

Page 5 - Overview

Site requirements 13 • Do not treat the water with softeners. Softeners can produce foam, which affects the operation of the unit. • Do not use we

Page 6 - Site safety and security

Site requirements 14 Parameter Range Calcium hardness (CaCO3) 0–200 ppm Magnesium hardness (CaCO3) 0–150 ppm Copper (Cu) < 0.20 ppm Iron (Fe) &l

Page 7 - HP POD 20c capacities

Site requirements 15 • Distance between possible UPS or generator locations and the HP POD 20c • Requirements for routing electrical feeders (unde

Page 8 - Site requirements

Supported facility connections 16 Supported facility connections Environmental control system The ECS developed for the HP water-cooled POD is a sta

Page 9 - End 1 view clearances shown

Supported facility connections 17 End view shown Humidifier A dedicated water supply and approved drainage is required for the humidifier. For mor

Page 10 - Future expansions

Supported facility connections 18 HP POD 20c access control The HP POD 20c is equipped with standard key lock hardware for each personnel entry door

Page 11 - Grounding requirements

Supported facility connections 19 Front view shown You must make the connections between the facility and the HP POD 20c. For configuration and ins

Page 12 - Utilities

© Copyright 2013 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Page 13 - Chilled water supply

Supported facility connections 20 You must make the connections between the facility and the HP POD 20c. For configuration and installation instruct

Page 14 - Piping materials

Environmental considerations 21 Environmental considerations Environmental risks • Avoid placing the HP POD 20c directly along a drainage path or i

Page 15 - Site electrical system

Site plan requirements and actions 22 Site plan requirements and actions Completing a site assessment HP requires a detailed site assessment prior t

Page 16 - Environmental control system

Site plan requirements and actions 23 • Ensure that the site safety and security programs are properly administered. • Interface directly with the

Page 17 - Humidifier

Site plan requirements and actions 24 • Assembly equipment locations Item Description 1 Crane 2 Reach 3 Truck 4 Area clear for scissors lift and

Page 18 - Fire box

Site plan requirements and actions 25 Additional structures If a customer-provided vestibule or other structure is installed and connected to the HP

Page 19 - Demarcation box

Appendix A: HP site assessment 26 Appendix A: HP site assessment HP POD 20c site assessment checklist During a survey of the readiness of a proposed

Page 20

Appendix A: HP site assessment 27 Item Description Yes No N/A Initial 8. Clearances Inspect the proposed installation site to confirm clearance

Page 21 - Environmental considerations

Appendix A: HP site assessment 28 Item Description Yes No N/A Initial 15. Recommendations Following the HP installation site visit, analyze the

Page 22 - Project coordination

Appendix B: Preparing for delivery 29 Appendix B: Preparing for delivery Pre-delivery tasks Allow adequate time for planning, scheduling, obtaining

Page 23 - Site planning

Contents 3 Contents Overview ...

Page 24

Appendix B: Preparing for delivery 30 Item Description Initial 10 Verify that the site location has clearances for the HP POD 20c installation, in

Page 25 - Additional structures

Appendix B: Preparing for delivery 31 Item Description Initial 2 Verify that the chilled water supply temperature meets the minimum POD chilled wa

Page 26

Appendix C: Regulatory compliance notices 32 Appendix C: Regulatory compliance notices HP POD 20c regulatory compliance The HP POD 20c complies with

Page 27

Appendix C: Regulatory compliance notices 33 Feature Specification Class Class1 Ambient temperature 2°C to 54°C (35.6°F to 129.2°F) Relative humidi

Page 28 - Item Description Initial

Glossary 34 Glossary APJ Asia Pacific Japan BMS building management system door A hinged portion of an enclosure that covers an opening. ECS envi

Page 29 - Pre-delivery tasks

Glossary 35 inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the e

Page 30 - Chilled Water Supply

Documentation feedback 36 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat

Page 31

Index 37 A about this guide 5 areas prone to lightning or power surges 21 assembly 29 assembly area 23 C capacity limitations 7 clearance

Page 32 - Safety and IEC compliance

Index 38 site planning considerations 23 site preparation 6 site preparation checklist 29 site requirements 8, 22 storage locations 24 sup

Page 33 - Warranty information

Contents 4 Zoning and permit requirements ...

Page 34 - Glossary

Overview 5 Overview About this document This document outlines the site and preparation requirements for a 6 m (20 ft) HP POD 20c as it is being rel

Page 35 - Glossary 35

Overview 6 Feature Specification Class Class1 Ambient temperature 2°C to 54°C (35.6°F to 129.2°F) Relative humidity 0% to 100% humidity • As part

Page 36 - Documentation feedback

HP POD 20c capacities 7 HP POD 20c capacities HP POD 20c capacity limitations The capacity limitations for the HP POD 20c are separated into two cat

Page 37 - Index 37

Site requirements 8 Site requirements Site pad The structural design of the HP POD 20c site pad must be based on the specific weight load of the com

Page 38 - Index 38

Site requirements 9 End 1 view clearances shown Top view keep-out and door swing clearances shown (shaded areas indicate the required clearance)